Component measurements
Resistance measured with the unit switched off, at approx. 20°C, unless stated otherwise.
Compressor
Measure at the compressor terminals or on the supply wire conductors.
| Component | Value |
|---|---|
| Winding (UV = UW = VW) | 1–5 Ω |
| Insulation: winding → casing | > 10 MΩ |
Transformer
To check that the transformer is working correctly, measure the resistance between the terminals.
| Component | Value |
|---|---|
| Resistance between terminals (normal state) | 0.1–1 Ω |
4-way valve — coil
AC supply. Cooling mode: 0 V. Heating mode: 230 V.
| Component | Value |
|---|---|
| 4-way valve coil | approx. 2 kΩ ±6% |
EEV valve — coil (winding groups)
The coil has 2 winding groups — measure each group individually. If the result deviates significantly from the table, the EEV coil is damaged.
| White | Yellow | Orange | Blue | Brown | Red | |
|---|---|---|---|---|---|---|
| White | 0 | ∞ | 92 | ∞ | 46 | ∞ |
| Yellow | ∞ | 0 | ∞ | 92 | ∞ | 46 |
| Orange | 92 | ∞ | 0 | ∞ | 46 | ∞ |
| Blue | ∞ | 92 | ∞ | 0 | ∞ | 46 |
| Brown | 46 | ∞ | 46 | ∞ | 0 | ∞ |
| Red | ∞ | 46 | ∞ | 46 | ∞ | 0 |
Values in Ω.
Fan motor — 3-pin DC
Measure resistance with the unit switched off. Always A = B = C.
| Component | Value |
|---|---|
| A: White – Red | 99 Ω ±7% |
| B: White – Yellow | 99 Ω ±7% |
| C: Yellow – Red | 99 Ω ±7% |
Fan motor — AC
Logic: A = B + C (569 = 251 + 318). Black–Red: run winding. Black–White: start winding. White–Red: common winding. If the blade turns with noticeable resistance, the motor is damaged. Also check the capacitance of the run capacitor on the board.
| Component | Value |
|---|---|
| A: Red – White | 569 Ω |
| B: Red – Black | 251 Ω |
| C: Black – White | 318 Ω |
Fan motor — 5-pin DC (diode test, motor disconnected)
Meter's red probe to GND (Black pin), black probe in turn to each of the remaining pins.
| Component | Value |
|---|---|
| Vm (Red) – GND | 0.7–0.9 V |
| VCC (White) – GND | 0.4–0.6 V |
| FG (Blue) – GND | 1.5–2.0 V |
| Vsp (Yellow) – GND | 0.8–1.2 V |
Fan motor — 5-pin DC (unit running)
Voltage measured under load, with the motor connected.
| Component | Value |
|---|---|
| Supply: Black (GND) – Red (Vm) | ≈ 310 V |
| Control: Black (GND) – White (VCC) | ≈ 15 V |
| Speed: Black (GND) – Yellow (Vsp), idle | 0 V |
| Low speed | ≈ 2.72 V |
| Medium speed | ≈ 3.35 V |
| High speed | ≈ 3.74 V |
Stepper motor (louver) — resistance measurement
Measure the resistance between each pair of stepper motor pins.
| Red | Orange | Yellow | Pink | Blue | |
|---|---|---|---|---|---|
| Red | 0 | 187 | 187 | 187 | 187 |
| Orange | 187 | 0 | 374 | 374 | 374 |
| Yellow | 187 | 374 | 0 | 374 | 374 |
| Pink | 187 | 374 | 374 | 0 | 374 |
| Blue | 187 | 374 | 374 | 374 | 0 |
Values in Ω.
Condensate pump + condensate level sensor (LCAC — cassette / duct)
Once the condensate level sensor is triggered, the pump is powered. About 25 s after the condensate has been pumped out (the float drops), power to the pump is cut off.
| Component | Value |
|---|---|
| Condensate pump | 435 Ω ±8% |
| Condensate level sensor | ≤ 0.4 Ω ±8% |