R290

Error codes

1Outdoor temperature thermistor failure
Causes
• Outdoor temperature thermistor failure (Ta)
• Incorrect wiring,
• disconnected sensor wire,
• damaged wire,
• short circuit of wires
• main board failure
Solution
1) Check the condition of the temperature sensor Ta connector THM7 - measure its resistance and compare with the reading in the calculator available in the app and on the controller - if incorrect, replace the sensor
2) Measure the voltage on the Ta sensor socket, it should be about 5VDC, if incorrect, the board is damaged
13Inverter overcurrent protection tripped
Causes
• Inverter overcurrent protection tripped
• Operation under overload,
• Compressor failure
• Incorrect voltage on the outdoor unit
• Check the pressure in the circuit
• Check the fan operation and the condition of the heat exchanger
Solution
1) Check the power supply voltage whether it is in the range 198-264V, check when stopped and during operation whether it is stable.
2) If the compressor starts but the error appears:
- Check the pressure in the circuit
- Check the refrigerant charge, possible excessive amount of refrigerant in the compressor
- Check the fan operation and whether the heat exchanger is not blocked
- Check the operation of the EEV valve and whether the refrigerant pipes are not blocked
3) Check the compressor resistance, see the measurement tables in the app
4) If the compressor does not start - failure of the inverter board or the compressor
14Protective device tripped (high pressure switch)
Causes
• Protective device tripped (high pressure switch)
• Outdoor unit: insufficient air flow through the outdoor unit heat exchanger during cooling mode
• Indoor unit: insufficient water flow through the indoor unit heat exchanger during heating mode
• Malfunction or failure of the expansion valve
• Water temperature in the indoor unit too high
• High pressure switch failure
• Excessive refrigerant charge
• Non-condensable gas in the refrigerant circuit
• Blocked discharge pipe
• Liquid line shut-off valve or gas line shut-off valve closed
Solution
1) Check the water flow through the hydro unit, remove dirt from the heat exchanger or elements blocking the flow
2) Check the water pump operation, verify according to error code 8D/51
3) Check whether the high pressure switch is correctly connected to the connector on the main board:
- R290 5-10kW - PCN401 (33Bar)
4) Check whether the high pressure switch is continuously shorted after the unit has stopped, if not check the pressure in the circuit, if it is below the switch activation value, the switch is damaged or blocked, try to knock on it mechanically to see if the relay releases. If not, replace the switch.
5) Check the expansion valve wiring
6) Check the expansion valve operation, when power is reset the expansion valve always tends to fully close, you can listen to check whether it works correctly.
7) Check the compressor discharge gas thermistor operation and mounting, replace if damaged
8) Check the water circuit temperature - too high above the operating envelope, make sure the water temperature sensors work correctly
9) Provide proper clearance around the outdoor unit
10) Check the fan motor operation
17Compressor discharge gas temperature thermistor failure (Td)
Causes
• Compressor discharge gas temperature thermistor failure (Td)
• Incorrect wiring,
• disconnected sensor wire,
• damaged wire,
• short circuit of wires
• main board failure
Solution
1) Check the condition of the temperature sensor Td connector THM9 - measure its resistance and compare with the reading in the calculator available in the app and on the controller - if incorrect, replace the sensor
2) Measure the voltage on the Td sensor socket, it should be about 5VDC, if incorrect, the board is damaged
18Incorrect inverter voltage
Causes
• Incorrect inverter voltage
• Voltage drop in the outdoor unit, check whether the power supply is correct
Solution
1) Voltage drop in the outdoor unit, check whether the power supply is correct within the range 230V +/- 10% or 380-415V +/- 10% when the unit is stopped and during its operation, if correct - the outdoor unit main board is damaged.
2) Check whether the N wire is damaged or loose

192nd heat exchanger liquid pipe temperature thermistor failure (Te2)
Compressor suction temperature sensor failure (Ts)
Causes
• 2nd heat exchanger liquid pipe temperature thermistor failure (Te2)
• Incorrect wiring,
• disconnected sensor wire,
• damaged wire,
• short circuit of wires
• main board failure
Solution
1) Check the condition of the temperature sensor Ts connector THM81 - measure its resistance and compare with the reading in the calculator available in the app and on the controller - if incorrect, replace the sensor
2) Measure the voltage on the sensor socket, it should be about 5VDC, if incorrect, the board is damaged

22Heat exchanger liquid pipe temperature thermistor failure (Te)
Causes
• Heat exchanger liquid pipe temperature thermistor failure (Te)
• Incorrect wiring,
• disconnected sensor wire,
• damaged wire,
• short circuit of wires
• main board failure
Solution
1) Check the condition of the temperature sensor Te connector THM8 - measure its resistance and compare with the reading in the calculator available in the app and on the controller - if incorrect, replace the sensor
2) Measure the voltage on the Te sensor socket, it should be about 5VDC, if incorrect, the board is damaged

43Incorrect operation of the outdoor unit high pressure sensor (Pd)
Causes
• Incorrect operation of the high pressure sensor (Pd)
• incorrect wiring,
• disconnected sensor wire,
• damaged wire,
• short circuit of wires
• module main board failure
Solution
1) Check the wiring of the pressure sensor on the outdoor unit main board connector CN4
2) Check the voltage 5VDC between pin 1 and 3 on the CN4 connector, if different replace the indoor unit main board
3) Check the voltage between pins 2 and 3 on the CN4 connector with the sensor plugged in, if outside the range 0.1V-4.9V replace the pressure sensor

47Increased discharge gas temperature
Causes
• Increased discharge gas temperature
• Low refrigerant charge,
• clogged pipes,
• thermistor failure,
• incorrect wiring
• Incorrect pipe connection,
• expansion valve blocked in the closed position
• Outdoor unit main board failure
Solution
1) Check the condition of the temperature sensor THM9 (Td) - measure its resistance and compare with the reading in the calculator available in the app and on the controller - if incorrect, replace the sensor
2) Measure the voltage on the Td sensor socket, it should be about 5VDC, if incorrect, the board is damaged
3) Check the expansion valve operation whether it is not stuck in the partially closed position - replace if damaged
4) Measure the resistance of the expansion valve coil, the measurement table is available in the app
5) Check the operation of the circulation pump, replace if damaged
6) Check the refrigerant charge in the circuit, if incorrect find the cause of the leak, repair it and refill the circuit with the correct amount of refrigerant
48Incorrect operation of the fan motor
Causes
• Fan controller protection tripped
• Incorrect rotational speed of the fan motor
• Is the outdoor unit fan exposed to wind gusts? - in this situation the error may occur.
• Blocked fan
• Incorrect fan operation
• Incorrect connection of wires on the CN14 connector
Solution

1) Is the outdoor unit fan exposed to wind gusts? - in this situation the error may occur.
2) Check whether the fan is not blocked
3) Check the CN14 connector on the outdoor unit main board
4) Measure the fan motor resistance, see the measurement tables in the app
51Water flow alarm
Causes
• Incorrect flow alarm in the hydraulic circuit (WP1)
• Incorrect water flow in the
hydraulic circuit
• Dirty water filter
• Restricted water flow through the heat exchanger
• Air lock in the system
• Failure of the main board or circulation pump
Solution
1) Check the water flow in the installation, whether it is not too low or too high, see the flow table.
2) Check the pump operation according to error code 75/8D
3) Check the condition of the filters in the installation
4) Check the opening of the ball valves
5) Bleed the system, make sure the pump is correctly bled and check the water pressure in the installation. In INTEGRA, air lock of the inside of the circulation pump is possible!
6) If the pump still does not start, possible failure of the main board or the circulation pump
5CDischarge gas temperature drop
Causes
• Discharge gas temperature drop
• Excessive refrigerant charge
• temperature sensor failure
• incorrect wiring
• Incorrect pipe connection,
• expansion valve blocked in the open position
• Outdoor unit main board failure
Solution
1) Check the condition of the temperature sensor THM9 (Td) - measure its resistance and compare with the reading in the calculator available in the app and on the controller - if incorrect, replace the sensor
2) Measure the voltage on the Td sensor socket, it should be about 5VDC, if incorrect, the board is damaged
3) Check the high pressure value in the circuit
4) Check the expansion valve operation whether it is not blocked in the open position, replace if damaged
5) If the unit is 10-16kW, check the operation of the bypass valve to make sure it is not in the open position
6) Check the refrigerant charge in the circuit, an excessive amount is possible if the expansion valve and the Td sensor work correctly
7) Check the fan operation - replace if damaged
8) Measure the fan motor resistance, the measurement table is available in the app
5DCritical refrigeration circuit alarm
System reset forbidden without technician inspection
Causes
• Compressor protection alarm (it is not possible to clear the alarm on the wired controller)
This alarm code appears when the following alarms occur three times within 6 hours”
*02, 07, 08, 43 to 45, 47
Solution
The system should not be restarted without first checking the cause of the alarm, it may lead to serious damage of the outdoor unit.
1) Check the error code on the 7-segment display of the outdoor or indoor unit
2) Check the alarm history on the controller or outdoor unit.
On the outdoor unit hold PSW2 -> Press PSW2 until you find position no01-no02 etc. Read the alarm code AC.... D1.... IT......
Follow the instructions for the indicated alarm code
3) Perform a power reset of the system to clear the alarm
64Communication error between indoor unit and outdoor unit
Causes
• Communication error between indoor unit and outdoor unit
• Incorrect connection of the communication wires
• loose terminals,
• disconnected power or communication wire
• blown fuse in the indoor or outdoor unit
• power failure of the indoor or outdoor unit
• main board failure
Solution
1) Check the status of the LEDs on the boards:
- outdoor unit - a red LED should light up on the board with the display
- indoor/hydro unit board - red LED1 should light up,
2) Check the power supply of the units if the LEDs do not light up as above
3) Check the condition of the fuses in the outdoor and indoor unit,
4) Read the error code from the controller, the indoor unit board, the outdoor unit board
4.1) controller R290= 64, indoor unit board 64, outdoor unit board 64 -> error concerns communication between the outdoor unit and the indoor unit.
• Check the condition of the communication wires between the outdoor and indoor unit - was a shielded wire used and is it correctly grounded at only one point?
• Check in the indoor unit whether the CN1 plug on the main board and the CN2 plug on the PCB4 board (diagram located on the unit plate) are correctly plugged in and the wires are not damaged
• Check whether the resistance on communication terminals 1/2 is about 75 Ohm
• Check whether the DSW setting regarding the refrigeration circuit address and unit type is consistent
4.2) controller 64, indoor unit board 65, outdoor unit board none (only red LED lit) -> the problem concerns controller - indoor unit board communication.
• follow error code 65
4.3) controller 64, indoor unit board 001F2F (LEDs lit correctly), outdoor unit board none (only red LED lit) -> the problem concerns controller - indoor unit board communication.
• follow error code 65
4.4) controller 64, indoor unit board none (LEDs lit correctly), outdoor unit board 64 -> the problem is with the indoor unit board.
• try to update the main board software, if it does not help replace the board.
5) Check the boards for electrical damage
46Communication error between the outdoor unit main board and the inverter
Causes
• Communication error between the outdoor unit main board and the inverter
• Loose terminals,
• damaged wire,
• blown fuse
• Outdoor unit main board failure
Solution
1) Check the LED status LED2 Red on the outdoor unit main board:
- if the LED is lit or off, replace the outdoor unit main board
- blinking means normal operation
2) Check the wiring between the main board and the inverter board
3) Check the condition of the fuses on the main boards
65Communication error between the unit and the main controller
Causes
• Communication error between the unit and the main controller
• Lack of communication between the unit and the main controller for a continuous period of 5 minutes.
• Damaged or not connected communication wires in the controller
• Damaged controller power wire, only Split version.
• Damaged controller
• Main board failure
Solution
1) Check the controller wiring, insertion into the A/B terminals, the connecting plug and the connection inside the controller
2) Check whether the wire between the CN1 socket on the main board and CN2 on the PCB4 board is not damaged or disconnected.
3) Check whether there is a voltage of 15VDC on the controller communication output A/B (units before 03.2023) or 24VDC newer. Check the same on the CN1 connector pins 3/4, if the voltage is incorrect replace the board
4) Check whether the controller displays the communication software version and whether it is correct
6AInverter failure
Causes
• Inverter failure
• Outdoor unit main board failure
• Voltage loss on one phase
• Main board failure
Solution
1) Turn off the power (LED1 on the outdoor unit main board is off) and restart, if the alarm code appears again replace the main board.
2) Check the noise filter
3) Read the inverter stop code from the outdoor unit display iTC
6BInverter heatsink temperature error
Causes
• Inverter heatsink temperature error
• Inverter heatsink thermistor failure,
• inverter heatsink thermistor protection tripped, temperature above 75 °C
• Loose main board mounting screws or incorrect contact
• Blocked outdoor unit heat exchanger
• Damaged main board
Solution
1) Check whether the outdoor unit starts after power reset, if the error still appears replace the main board
2) Check whether there is proper contact between the transistor module and the heatsink and whether the mounting screws are correctly tightened
3) Check whether the outdoor unit heat exchanger is not blocked and whether the fan works correctly,
4) check whether the inverter board heatsink is clean and properly fastened to the main board
6CInverter error signal detected
Causes
• Inverter error signal detected
• Error signal detected (IPM module error, speed
fluctuation, hardware error of the power factor correction circuit)
• Damaged / loose power supply wires
• Main board failure
• Transistor module failure
• Compressor failure
• Blocked outdoor unit heat exchanger (no heat rejection)
Solution
1) Check whether the outdoor unit starts after power reset, if not check:
- compressor condition
- pressure in the installation
- whether the heat exchangers are not blocked
- fan operation
2) Check the iTC code status on the outdoor unit display:
- iTC = 1 IPM module error of the main board
- iTC = 21 Inverter speed fluctuation detected, possible problems with the power supply voltage on the board e.g. loose N wire.
- iTC = 12 only 10 to 16kW models, compressor ground short circuit detected
- iTC = 23 Abnormal PFC (power factor correction) circuit operation, only 4-8kW models
3) Check the connection of the power supply wires
4) Turn off the power, disconnect the compressor power supply and restart, is the safety function activated? Check the iTC error status on the outdoor unit display, if after disconnecting the compressor = 13, check the compressor resistance. The board should be OK
5) Check the compressor resistance, see the measurement tables in the app
6) Check the condition of the transistor module
7) Check the condition of the main board for burn marks
6DInverter current sensor failure
Causes
• Incorrect operation of the inverter current sensor
• Current sensor failure / inverter board failure
• Compressor failure
• Incorrect power supply
Solution
1) Check whether the power supply voltage of the inverter board is correct 198-264V -> if not correct replace the transistor module
2) Check whether the compressor operates after restarting - if the compressor does not operate and error P17 is displayed, check the compressor resistance -> if incorrect, replace the compressor
If the compressor resistance is correct -> replace the main board
3) Check the compressor resistance, see the measurement tables in the app
6ELow pressure circuit pressure drop protection tripped (vacuum protection)
Causes
• Low pressure circuit pressure drop protection tripped (vacuum protection)
• Low refrigerant charge,
• Clogged pipes,
• Expansion valve blocked in the
closed position (loose connector)
• Closed shut-off valve
• Outdoor unit fan motor failure
Solution

1) Check whether the refrigerant pipes are not damaged or blocked
2) Check the operation of the expansion valve and the valve coil - it may be blocked in the closed position,
3) Check the resistance of the expansion valve coil, see the measurement tables in the app
4) Check the operation of the outdoor unit fan - possible failure
5) Measure the fan motor resistance, see the measurement tables in the app
6) Check the condition of the compressor discharge thermistor Td and measure its resistance
7) Check the refrigerant charge,
79Incorrect capacity setting of the outdoor unit and indoor unit
Causes
• Incorrect capacity setting of the outdoor unit and indoor unit
• Incorrect address setting of the outdoor and indoor unit
Solution
1) Check the setting of the DSW3 switch of the outdoor unit - if incorrect, set the correct value
2) Check the setting of the DSW2 switch of the indoor unit - if incorrect, set the correct value
3) Check the setting of the DSW4 switch in the outdoor unit and DSW8 in the indoor unit - set them the same
7AHigh pressure circuit pressure drop protection tripped
Causes
• High pressure circuit pressure drop protection tripped
• Low refrigerant charge
• Reversing valve stuck in the middle position
• Incorrect refrigerant connection between the outdoor and indoor unit
• Water temperature at the inlet of the indoor unit too low
Solution

1) Check the operation of the 4-way valve whether it is not in the middle position
2) Check the refrigerant connection between the outdoor and indoor unit
3) Check whether the water temperature at the inlet of the indoor unit is not too low - see error code 11
4) Check whether the outdoor temperature indicated by the sensor on the outdoor unit is not too low - see error code 22
5) Check the refrigerant charge
7CLow compression ratio protection tripped
Causes
• Low compression ratio protection tripped
• Incorrect compression (inverter or compressor failure, or 4-way valve, loose power supply wires)
Solution
1) Check whether the compressor operates
2) Check the operation of the 4-way valve - whether it works and switches correctly, verify its operation based on the temperatures at the ports
3) Check the compression ratio condition:
Compression ratio ε = ( Pd [MPa] + 0.1)/(Ps [MPa] + 0.06)
Pd: high pressure (discharge pressure)
Ps: low pressure (suction pressure)
7FIncorrect address setting of the indoor unit
Causes
• Incorrect address setting of the indoor unit
Solution
1) Check the setting of the DSW4 switch in the outdoor unit and DSW8 in the indoor unit - set them the same
82Refrigerant liquid pipe thermistor failure (TL)
Causes
• Refrigerant liquid pipe thermistor failure (TL)
• Incorrect wiring,
• disconnected sensor wire,
• damaged wire,
• short circuit of wires
• failure of the hydro module main board
Solution
1) Check the condition of the temperature sensor (TL) connector THM5 - measure its resistance and compare with the reading in the calculator available in the app and on the controller - if incorrect, replace the sensor
2) Measure the voltage on the TL sensor socket, it should be about 5VDC, if incorrect, the board is damaged

84Refrigerant gas pipe thermistor failure (Tg)
Causes
• Refrigerant gas pipe thermistor failure (Tg)
• Incorrect wiring,
• disconnected sensor wire,
• damaged wire,
• short circuit of wires
• failure of the hydro module main board
Solution
1) Check the condition of the temperature sensor (Tg) connector THM4 - measure its resistance and compare with the reading in the calculator available in the app and on the controller - if incorrect, replace the sensor
2) Measure the voltage on the Tg sensor socket, it should be about 5VDC, if incorrect, the board is damaged


87Return water thermistor failure (Tiw)
Causes
• Return water thermistor failure (Tiw)
• Incorrect wiring,
• disconnected sensor wire,
• damaged wire,
• short circuit of wires
• failure of the hydro module main board
Solution
1) Check the condition of the temperature sensor (Tiw) connector THM2 - measure its resistance and compare with the reading in the calculator available in the app and on the controller - if incorrect, replace the sensor
2) Measure the voltage on the Tiw sensor socket, it should be about 5VDC, if incorrect, the board is damaged
88Supply water thermistor failure (Tow)
Causes
• Supply water thermistor failure (Tow)
• Incorrect wiring,
• disconnected sensor wire,
• damaged wire,
• short circuit of wires
• failure of the hydro module main board
Solution
1) Check the condition of the temperature sensor (Tow) connector THM1 - measure its resistance and compare with the reading in the calculator available in the app and on the controller - if incorrect, replace the sensor
2) Measure the voltage on the Tow sensor socket, it should be about 5VDC, if incorrect, the board is damaged
8CFlow sensor error
Causes
• Flow sensor alarm
• Main board or flow sensor failure
Solution
1) Check the wiring of the flow sensor on the indoor unit main board connector CN9
2) Check the voltage 5VDC between pin 1 and 3 on the CN9 connector, if different replace the indoor unit main board
3) Check the voltage between pins 2 and 3 on the CN9 connector with the sensor plugged in, if outside the range 0.1V-4.9V replace the flow sensor

8DWater pump failure (WP1)
Causes
• Water pump failure (WP1)
• Incorrect operation of the iPWM system of water pump 1
• Check the water pump operation
• Damaged PWM wires
• Voltage on the circulation pump outside the allowable range
• External flow
Solution
1) Check whether the pump is connected correctly / check the wiring
2) Check whether there is power supply on the PCN26 connector and whether the PWM wire of the CN19 socket is correctly plugged in
3) Check the iPWM-out parameter on the indoor unit main board display -> Press PSW2 for 3 seconds -> Use the PSW2 button to find the o-P option -> read the indication and check what it means in the diagnosis of the water pump WP1
4) Check whether the pump is not blocked and whether the supply voltages to the hydro module are correct
8EWater overheating protection in Circuit 2
Causes
• Water overheating protection in Circuit 2
• Water supply temperature in circuit 2 higher than the set temperature + allowable increase (Check the parameter setting in the service menu KompenZabezPrzegrz) maintained for 10 min
• Check the operation of the mixing valve
Solution
1) Check the parameter setting in the service menu Menu -> Configuration -> Heating -> Circuit 2 -> Overheat protection
2) Check the operation of the mixing valve
3) Check the operation of the circulation pumps after the mixer
4) Check whether the electric heater is not switched on, whether there is no short circuit on the heater contactors
5) Check the condition of the temperature sensor (Tow2) - measure its resistance and compare with the reading in the calculator available in the app and on the controller - if incorrect, replace the sensor
6) Measure the voltage on the Tow2 sensor socket, it should be about 5VDC, if incorrect the board is damaged, also check the wire between the main board and the auxiliary board PCB4, see the wiring diagram
8FFreeze protection disabled by the indoor unit temperature thermistors
Causes
• Freeze protection disabled by the indoor unit temperature thermistors
• Water or refrigerant temperature is
too low and activates the freeze protection
• Check the temperature and mounting of the Tg, TL, TowHp sensors
• Incorrect refrigerant charge
• Blocked plate heat exchanger
• Expansion valve failure
• Flow problem
• Problem with the water volume in the installation
• Air lock in the system
• Failure of the main board or circulation pump
Solution
1) Check whether the measured refrigerant and water temperature Tg(THM4), TL(THM5), TowHp(THM3) is correct, if the sensors are not damaged check the temperature readings on the main controller, if different from what the resistance indicates -> replace the main board,
2) Check the refrigerant charge
3) Check whether the heat exchanger is not blocked, check the filters and the flow in the installation
4) Check the water volume in the installation
5) Check the operation of the expansion valve,
6) Check the operation of the system in another operating mode
9AAuxiliary electric heater safety thermostat tripped
Causes
• Auxiliary electric heater safety thermostat tripped
• Temperature of the auxiliary electric heater
too high >75 °C
• Check the contact of the auxiliary electric heater safety thermostat TCO-L (230V)
• Check the heater fuse TFe
Solution
1) Check the temperature in the heating circuit -> if it is above 75°C +/- 4°C the heater thermostat has tripped, wait until the temperature drops and check again whether the error code still occurs
2) Check for a short circuit on the heater thermostat The terminal on the board PCN5
No short circuit - damaged thermostat (caution 230V on the main board)
3) Check the internal thermostat of the heater when the error does not occur but the heater does not work.
- R290 MONOBLOK 050-100 - Check the contact condition between TH1 - TH2, there should be a short circuit
- R290 HYDRO 050-100 - Check the operation of the automatic thermostat TCO2
9BDHW electric heater safety thermostat tripped
Causes
• DHW electric heater safety thermostat tripped
• Temperature of the DHW electric heater
too high
• Safety device of the DHW heater DHWTHe2 (Input 12) not connected
Solution
1) INTEGRA: Check the temperature in the DHW tank - if it is too high the protection may have tripped, wait until it drops below 45 degrees and reset the thermostat which is located inside the unit. If it does not help, check the thermostat connection on the board to the DHWTHe2 terminals (Input 12)
2) HYDROSPLIT/MONOBLOK: Check the status of the thermal protection of the heater DHWTHe2 (Input 12), if the DHW heater is activated in the system the board must receive a short circuit signal on these terminals. If you do not use the output signal for the DHW heater from the pump, simply deactivate the heater in the configuration.
9CWater pressure alarm
Causes
• Water pressure alarm
• Water pressure in the hydraulic circuit outside the range 1-3bar
• Damaged water pressure sensor in the hydraulic module
• Air lock in the hydraulic module
• Failure of the hydraulic module main board
Solution
1) Check the water pressure value in the hydraulic circuit
2) If the pressure is above 3 bar, check the operation of the safety valve, reduce the water pressure in the installation to the range from 1 to 3 bar
3) Air lock in the hydraulic module
4) Check the wiring of the pressure sensor on the indoor unit main board connector CN6
5) Check the voltage 5VDC between pin 1 and 3 on the CN6 connector, if different replace the indoor unit main board
6) Check the voltage between pins 2 and 3 on the CN6 connector with the sensor plugged in, if outside the range 0.1V-4.9V replace the pressure sensor
7) For the duration of the repair you can cancel this alarm code by changing DSW3-3 to ON
9DWater pressure sensor failure (Pw)
Causes
• Water pressure sensor failure (Pw)
• Incorrect wiring,
• disconnected sensor wire,
• damaged wire,
• short circuit of wires
• failure of the hydro module main board
Solution
1) Check the wiring of the pressure sensor on the indoor unit main board connector CN6
2) Check the voltage 5VDC between pin 1 and 3 on the CN6 connector, if different replace the indoor unit main board
3) Check the voltage between pins 2 and 3 on the CN6 connector with the sensor plugged in, if outside the range 0.1V-4.9V replace the pressure sensor
4) For the duration of the repair you can cancel this alarm code by changing DSW3-3 to ON

9EHeat pump outlet water thermistor failure (TowHP)
Causes
• Heat pump outlet water thermistor failure (TowHP)
• Incorrect wiring,
• disconnected sensor wire,
• damaged wire,
• short circuit of wires
• failure of the hydro module main board
Solution
1) Check the condition of the temperature sensor TowHP connector THM3 - measure its resistance and compare with the reading in the calculator available in the app and on the controller - if incorrect, replace the sensor
2) Measure the voltage on the TowHP sensor socket, it should be about 5VDC, if incorrect, the board is damaged




9FDHW thermistor failure (TDHW)
Causes
• DHW thermistor failure (TDHW)
• Incorrect wiring,
• disconnected sensor wire,
• damaged wire,
• short circuit of wires
• failure of the hydro module main board
Solution
1) Check the condition of the temperature sensor (TDHW) connector THM7/A8 - measure its resistance and compare with the reading in the calculator available in the app and on the controller - if incorrect, replace the sensor
2) Measure the voltage on the TDHW sensor socket, it should be about 5VDC, if incorrect, the board is damaged



A1Auxiliary sensor failure (Tow3)
Causes
• Auxiliary sensor failure (Tow3)
• Loose, disconnected, damaged or shorted connector.
• hydraulic separator operation mode is enabled, but the Tow3 temperature has not been set in all auxiliary sensors (A1-A7).
Solution
1) Check the sensor configuration in the controller, set the sensor to no function in the configuration or disable the buffer/separator function if you do not have a sensor
2) Check the condition of the temperature sensor (Tow3), by default socket A1 - measure its resistance and compare with the reading in the calculator available in the app and on the controller - if incorrect, replace the sensor
3) Measure the voltage on the Tow3 sensor socket, it should be about 5VDC, if the board is OK, the problem is with the configuration or the sensor, if not check:
- whether the voltage 5VDC comes out of the main board THM8 socket, if not the main board is damaged, if yes check the wires or replace the PCB4 board.
- If the voltage on another auxiliary socket A1-A7 is correct, if possible move the sensor and change the configuration in the controller, there is no need to replace the main board
4) You can disable the sensor alarm by changing DSW7-2 to ON

A2Auxiliary sensor failure (Tswp)
Causes
• Auxiliary sensor failure (Tswp)
• Loose, disconnected, damaged or shorted connector.
• pool heating operation mode is enabled, but the Tswp temperature has not been set in all auxiliary sensors (A1-A7).
Solution
1) Check the sensor configuration in the controller, set the sensor to no function in the configuration or disable the pool function if you do not have a sensor
2) Check the condition of the temperature sensor (Tswp), by default socket A3 - measure its resistance and compare with the reading in the calculator available in the app and on the controller - if incorrect, replace the sensor
3) Measure the voltage on the Tswp sensor socket, it should be about 5VDC, if the board is OK, the problem is with the configuration or the sensor, if not check:
- whether the voltage 5VDC comes out of the main board THM9 socket, if not the main board is damaged, if yes check the wires or replace the PCB4 board.
- If the voltage on another auxiliary socket A1-A7 is correct, if possible move the sensor and change the configuration in the controller, there is no need to replace the main board

A3Auxiliary sensor failure (Tsolar)
Causes
• Auxiliary sensor failure (Tsolar)
• Loose, disconnected, damaged or shorted connector.
• solar installation operation mode is enabled, but the Tsolar temperature has not been set in all auxiliary sensors (A1-A7).
Solution
1) Check the sensor configuration in the controller, set the sensor to no function in the configuration or disable the solar function if you do not have a sensor
2) Check the condition of the temperature sensor (Tsolar), by default socket A2 - measure its resistance and compare with the reading in the calculator available in the app and on the controller - if incorrect, replace the sensor
3) Measure the voltage on the Tsolar sensor socket, it should be about 5VDC, if the board is OK, the problem is with the configuration or the sensor, if not check:
- whether the voltage 5VDC comes out of the main board THM10 socket, if not the main board is damaged, if yes check the wires or replace the PCB4 board.
- If the voltage on another auxiliary socket A1-A7 is correct, if possible move the sensor and change the configuration in the controller, there is no need to replace the main board

A4Auxiliary sensor failure (Tow2)
Causes
• Auxiliary sensor failure (Tow2)
• Loose, disconnected, damaged or shorted connector.
• second circuit operation mode is enabled, but the Tow2 temperature has not been set in all auxiliary sensors (A1-A7).
Solution
1) Check the sensor configuration in the controller, set the sensor to no function in the configuration or disable the second circuit function if you do not have a sensor
2) Check the condition of the temperature sensor (Tow2), by default socket A4 - measure its resistance and compare with the reading in the calculator available in the app and on the controller - if incorrect, replace the sensor
3) Measure the voltage on the Tow2 sensor socket, it should be about 5VDC, if the board is OK, the problem is with the configuration or the sensor, if not check:
- whether the voltage 5VDC comes out of the main board THM6 socket, if not the main board is damaged, if yes check the wires or replace the PCB4 board.
- If the voltage on another auxiliary socket A1-A7 is correct, if possible move the sensor and change the configuration in the controller, there is no need to replace the main board

A5Auxiliary sensor failure for DHW
Causes
• Auxiliary sensor failure for DHW
• Loose, disconnected, damaged or shorted connector.
• room temperature control has been activated but the sensor has not been connected to the correct socket
Solution
1) Check the sensor configuration in the controller, set the sensor to no function in the configuration if you do not have a sensor
2) Check the condition of the auxiliary DHW temperature sensor (TDHW1), by default socket A5 - measure its resistance and compare with the reading in the calculator available in the app and on the controller - if incorrect, replace the sensor
3) Measure the voltage on the TDHW1 sensor socket, it should be about 5VDC, if the board is OK, the problem is with the configuration or the sensor, if not check:
- whether the voltage 5VDC comes out of the main board THM11 socket, if not the main board is damaged, if yes check the wires or replace the PCB4 board.
- If the voltage on another auxiliary socket A1-A7 is correct, if possible move the sensor and change the configuration in the controller, there is no need to replace the main board

A6Auxiliary sensor A6 failure
Causes
• Auxiliary sensor A6 failure (room temperature)
• Loose, disconnected, damaged or shorted connector.
• room temperature control has been activated but the sensor has not been connected to the correct socket
Solution
1) Check the sensor configuration in the controller, set the sensor to no function in the configuration if you do not have a sensor
2) Check the condition of sensor A6 - measure its resistance and compare with the reading in the calculator available in the app and on the controller - if incorrect, replace the sensor
3) Measure the voltage on the A6 sensor socket, it should be about 5VDC, if the board is OK, the problem is with the configuration or the sensor, if not check:
- whether the voltage 5VDC comes out of the main board THM17 socket, if not the main board is damaged, if yes check the wires or replace the PCB4 board.
- If the voltage on another auxiliary socket A1-A7 is correct, if possible move the sensor and change the configuration in the controller, there is no need to replace the main board

A7Auxiliary sensor A7 failure
Causes
• Auxiliary sensor A7 failure (room temperature)
• Loose, disconnected, damaged or shorted connector.
• room temperature control has been activated but the sensor has not been connected to the correct socket
Solution
1) Check the sensor configuration in the controller, set the sensor to no function in the configuration if you do not have a sensor
2) Check the condition of sensor A7 - measure its resistance and compare with the reading in the calculator available in the app and on the controller - if incorrect, replace the sensor
3) Measure the voltage on the A7 sensor socket, it should be about 5VDC, if the board is OK, the problem is with the configuration or the sensor, if not check:
- whether the voltage 5VDC comes out of the main board THM18 socket, if not the main board is damaged, if yes check the wires or replace the PCB4 board.
- If the voltage on another auxiliary socket A1-A7 is correct, if possible move the sensor and change the configuration in the controller, there is no need to replace the main board

F1Critical refrigeration circuit alarm
Alarm generated by the outdoor unit (outdoor unit alarm 21-29)
Causes
• Alarm generated by the outdoor unit (outdoor unit alarm 21-29)
• Check the error code on the 7-segment display of the outdoor or indoor unit
• Perform a power reset of the system to clear the alarm
Solution
The system should not be restarted without first checking the cause of the alarm, it may lead to serious damage of the outdoor unit.
1) Check the error code on the 7-segment display of the outdoor or indoor unit
2) Check the alarm history on the controller or outdoor unit.
On the outdoor unit hold PSW2 -> Press PSW2 until you find position no01-no02 etc. Read the alarm code AC.... D1.... IT......
Follow the instructions for the indicated alarm code
3) Perform a power reset of the system to clear the alarm
F2Critical refrigeration circuit alarm
Alarm generated by the outdoor unit (outdoor unit alarm except 21-29 and EE)
Causes
• Alarm generated by the outdoor unit (outdoor unit alarm except 21-29 and EE)
• Check the error code on the 7-segment display of the outdoor or indoor unit
• Perform a power reset of the system to clear the alarm
Solution
The system should not be restarted without first checking the cause of the alarm, it may lead to serious damage of the outdoor unit.
1) Check the error code on the 7-segment display of the outdoor or indoor unit
2) Check the alarm history on the controller or outdoor unit.
On the outdoor unit hold PSW2 -> Press PSW2 until you find position no01-no02 etc. Read the alarm code AC.... D1.... IT......
Follow the instructions for the indicated alarm code
3) Perform a power reset of the system to clear the alarm
F3Critical refrigeration circuit alarm
Alarm generated by the outdoor unit (outdoor unit alarm EE)
Causes
• Alarm generated by the outdoor unit (outdoor unit alarm EE)
• Check the error code on the 7-segment display of the outdoor or indoor unit
• Perform a power reset of the system to clear the alarm
Solution
The system should not be restarted without first checking the cause of the alarm, it may lead to serious damage of the outdoor unit.
1) Check the error code on the 7-segment display of the outdoor or indoor unit
2) Check the alarm history on the controller or outdoor unit.
On the outdoor unit hold PSW2 -> Press PSW2 until you find position no01-no02 etc. Read the alarm code AC.... D1.... IT......
Follow the instructions for the indicated alarm code
3) Perform a power reset of the system to clear the alarm
H2Communication alarm between the wired controller and the main controller
Causes
• Communication alarm between the wired controller and the main controller
• The wired controller is configured as a room thermostat, but no wired controller has been detected in the installation
• Damaged communication wire of the room controller
• Duplicated address of the room controller if two are installed
• Perform a power reset of the system to clear the alarm
• Room controller failure
• Main PCB board failure
Solution
1) The wired controller is configured as a room thermostat in the controller, but the heat pump is not connected to any controller.
2) Damaged communication wire of the room controller
3) Incorrect or duplicated address of the room controller if two are installed - verify the address according to the installation manual
4) Perform a power reset of the system to clear the alarm after resolving it
5) Room controller failure
6) Check whether there is a voltage of 15VDC on the controller communication output A/B (units before 03.2023) or 24VDC newer. Check the same on the CN1 connector pins 3/4, if the voltage is incorrect replace the board