Outdoor unit
Function Change Procedure
Change functions ONLY when the outdoor unit is stopped. Condition: DIP switch DSW2-5 set to ON.
1
Entering settings mode
Set DIP switch DSW2-5 to ON.
The function code (e.g. FA) will appear on the 7-segment display.
The function code (e.g. FA) will appear on the 7-segment display.
2
Selecting a function
Use the PSW2 / PSW3 buttons to scroll between functions (FA, ni, GH, GC...).
3
Changing the value
Press PSW1 to change the function value (00 / 01).
4
Confirming
Hold PSW3 for approx. 4 seconds.
Buttons: PSW1 = change value (00/01) • PSW2 = next function • PSW3 = previous function
Factory default for all functions: "00" (Inactive / No setting). Note down the number of each function you change.
Function list (7-segment code)
1FACirculation function at Thermo-OFF (heating)
2niNight Shift (night mode / low noise)
3GHCancel outdoor temp. limit for heating
4GCCancel outdoor temp. limit for cooling
5JoDefrosting for cold zones (changed condition)
6E-SLo defrost setting (IU fan speed)
7HTCancel Hot Start
8cUPerformance priority mode — cooling
9hUPerformance priority mode — heating
10SCEnergy saving mode — cooling
11SHEnergy saving mode — heating
12nHCapacity correction for long pipes
13dBLow noise setting
14dEDemand function setting
15UEWave function setting
16FELow outlet temp. protection — cooling 1
17FcLow outlet temp. protection — cooling 2
18EiHeat exchanger superheat setting
19CoPerformance test setting
20F1Base pan heater
21F2DHW test
22F3Base pan heater turn-on temperature (00: -2°C / 01: 2°C)
23F4Base pan heater run time (00: 5-20 min / 01: 5-30 min)
24F5Oil heater function
Details of important functions
Jo — Defrosting for cold zones
00: standard control
01: defrost condition 2 for cold areas
Changes the defrost start/stop temperature thresholds. Set 01 in regions with prolonged frost, where standard defrosting is too infrequent.
01: defrost condition 2 for cold areas
Changes the defrost start/stop temperature thresholds. Set 01 in regions with prolonged frost, where standard defrosting is too infrequent.
cU — Cooling performance priority
00: normal
01: raised max. compressor frequency (cooling only)
Max. frequency [Hz]:
• 2.0 HP (050): 85 → 90
• 3.0 HP (080): 75 → 85
• 3.5 HP (100): 80 → 90
Use when cooling performance seems insufficient.
01: raised max. compressor frequency (cooling only)
Max. frequency [Hz]:
• 2.0 HP (050): 85 → 90
• 3.0 HP (080): 75 → 85
• 3.5 HP (100): 80 → 90
Use when cooling performance seems insufficient.
hU — Heating performance priority
00: normal
01: raised target compressor frequency (heating only)
Increases heating performance, especially at low outdoor temperatures. Values depend on ambient temperature and unit capacity (2.0 / 3.0 / 3.5 HP).
01: raised target compressor frequency (heating only)
Increases heating performance, especially at low outdoor temperatures. Values depend on ambient temperature and unit capacity (2.0 / 3.0 / 3.5 HP).
F3 / F4 — Base pan heater
F3 (turn-on temperature):
• 00: -2°C threshold (default)
• 01: 2°C threshold
F4 (run time):
• 00: 5-20 minutes (default)
• 01: 5-30 minutes
Prevents condensate from freezing in the pan. Set higher values in harsh climates.
• 00: -2°C threshold (default)
• 01: 2°C threshold
F4 (run time):
• 00: 5-20 minutes (default)
• 01: 5-30 minutes
Prevents condensate from freezing in the pan. Set higher values in harsh climates.