R290

Component measurements

Resistance measured at a temperature of 20 °C.
Pump model: 050 = 5 kW / 080 = 8 kW / 100 = 10 kW.
Reversing valve
ComponentModelResistancePump model
Reversing valve coilDXQ-9142085 Ω050 / 080 / 100
Electronic expansion valve (EXV)
ComponentModelResistancePump model
E-expansion valve coilPAM-MD12HQ-306150 Ω050 / 080 / 100
Compressor
ComponentModelResistancePump model
CompressorEDTM280D85EMTbetween windings 0.44 Ω, to ground >20MΩ050
CompressorEDTF420D64EMTbetween windings 0.63 Ω, to ground >20MΩ080 / 100
DC fan motor
ComponentModelResistancePump model
DC fan motorZWB4710L00AL17.8 Ω050 / 080 / 100