R290

Stop codes

Indicator L

0OKOperation stopped = switched off with the button
1OKThermostat off
2ERRORAlarm
3OKAnti-freeze or anti-overheat protection
5ERROROutdoor unit power supply problem – Reset
6ERRORIndoor unit power supply problem – Reset
7OKCooling: stopped due to too low outdoor temp.
Heating: stopped due to too high outdoor temp.
8ERRORCompressor problem
9OK4-way valve switching, unit stop
10OKForced shutdown
11WARNINGResume – pressure problem

Indicator R

12WARNINGResume – low pressure problem
13WARNINGResume – high pressure problem
14WARNINGResume – abnormal compressor voltage
15WARNINGResume – compressor/discharge temp. too high or suction pressure too low
16WARNINGResume – discharge temperature problem
17WARNINGResume – inverter disconnection
18WARNINGResume – due to voltage problems
19OKOperation mode change

Cause Code of Inverter Stoppage (iTC)

ITCStoppage CauseCorresponding cause code of I.U. or O.U. stoppageIndication during retryAlarm code
1IPM Error17P176c
2Instantaneous Overcurrent17P1713
3Inverter Fin Thermistor Protection Activation17P176b
4Electronic Thermal Protection17P1713
5Inverter Voltage Decrease18P1818
6Overvoltage18P1818
8The current Thermistor Protection Activation17P176d
12Ground Fault Detection from Compressor17P176c
17Communication Error18P186A
18Protection Device Actuation (PSH)13P1314
19Abnormal Protective Device--7d
21Step-Out Detection17P176c
Undefined Function18--

Cause of failure — details

Stoppage CauseITCCause of failure
IPM Error1The instantaneous current of the compressor output is too large, triggering the hardware protection.
Instantaneous Overcurrent2The compressor outputs overcurrent, and software protection is triggered when the effective value is greater than 16A (for 050) /18A (for 080-100).
Inverter Fin Thermistor Protection Activation3The IPM temperature is too high, check whether the IPM is in good contact with the fin.
Electronic Thermal Protection4The current thermistor detects Overcurrent
Inverter Voltage Decrease5The DC bus voltage is too low, check the input power voltage.
Overvoltage6The DC bus voltage is too high, check the input power voltage.
Abnormal fault of sampling circuit8When the frequency of the inverter passes 15~18Hz, the absolute value of the U phase ± and V phase ± detected by the current sensor is below 1.5A; or the position determines when the peak U-plane current at the end is below 5A
Ground Fault Detection from Compressor12Inverter PCB detects overcurrent when checking ground fault before compressor starts operation.
Open Phase Detection13There is no current or leakage of current in one phase of the three-phase output of the compressor. Please check
1. Whether the wiring of the compressor is correct;
2. Whether one phase of the compressor is open circuit;
3. Whether there is major leakage current between the compressor winding and Ground.
Protection Device activation (PSH)18High pressure switch circuit triggers protection, please check
1. Check whether the wiring of the high pressure switch is correct;
2. The high pressure is too high, causing the pressure switch to be activated;
3. The state of the high pressure switch is abnormal.
Step-Out Detection21The demagnetization of the compressor causes the compressor to step out. Please confirm whether the compressor is normal.

The actual rotating speed of the compressor does not match the target speed of the inverter, please confirm whether the compressor is normal.