WP1 pump
0The iPWM interface is short circuit• Faulty WP1 inside the indoor unit
• Faulty CN19 interface on I.U. PCB1ERROR
• Faulty CN19 interface on I.U. PCB1ERROR
2The pump is ready to run—OK
3The water flow is 0Release the alarm to retry running.WARNING
85Abnormal function mode. Pump has stopped but is still functional.• Undervoltage <160/170 V
• Overvoltage >250/270 V
• Unexpected external flowERROR
• Overvoltage >250/270 V
• Unexpected external flowERROR
90Abnormal function mode. Pump has stopped but is still functional.Check the installation setup and medium:
• Failure on another component than pump
• Debris in the installation
• Bad temperature setupERROR
• Failure on another component than pump
• Debris in the installation
• Bad temperature setupERROR
95The pump has stopped due to permanent failure• Overcurrent
• Overtemperature
• Pump blocked
• Electronic module out of orderERROR
• Overtemperature
• Pump blocked
• Electronic module out of orderERROR
100The iPWM interface is open circuit• Faulty WP1 inside the indoor unit
• Faulty CN19 interface on I.U. PCB1ERROR
• Faulty CN19 interface on I.U. PCB1ERROR