Protection codes
The protection control code is shown on the 7-segment display of the outdoor unit while a protection control is active, and it turns off when the protection control is canceled. If several protection controls are active, the code with the highest priority is displayed (1 = highest). If several retry controls are active, the code of the latest one is displayed.
The code format depends on the unit size: 044–080 — two characters (e.g. P1), 100–160 — three characters (e.g. P01).
| Priority | 044~080 | 100~160 | Protection control performed | Remark |
|---|---|---|---|---|
| 1 | P1 | P01 | Pressure ratio protection control (discharge-side pressure increase) | To control the compressor frequency for prevention of operation with high/low pressure ratio. |
| 2 | P2 | P02 | High pressure increase protection control | To control the compressor frequency for prevention of high pressure increase. |
| 3 | P3 | P03 | Inverter current protection control | To control the compressor frequency for prevention of inverter current increase in the outdoor unit during operation. |
| 4 | P4 | P04 | Inverter fin temperature increase protection control | To control the compressor frequency for prevention of inverter fin temperature increase. The inverter fin temperature is detected at the O.U. main PCB. |
| 5 | P5 | P05 | Discharge temperature increase protection control | To control the compressor frequency for prevention of discharge gas temperature increase during operation. |
| 6 | P6 | P06 | Low pressure decrease protection control | To control the compressor frequency for prevention of low pressure decrease. |
| 7 | Pd | P0d | Low pressure increase protection control | To control the compressor frequency for prevention of low pressure increase. |
| 8 | PA | P0A | Demand current control | To control the compressor frequency for fixing the inverter primary current around the set value (40~100% of rated current). |
| 9 | P9 | P09 | High pressure decrease protection control | To control the compressor frequency for prevention of high pressure decrease, which would interrupt smooth refrigerant distribution to indoor unit with different height and oil supply to the compressor. |