R32

Protection codes

The protection control code is shown on the 7-segment display of the outdoor unit while a protection control is active, and it turns off when the protection control is canceled. If several protection controls are active, the code with the highest priority is displayed (1 = highest). If several retry controls are active, the code of the latest one is displayed.

The code format depends on the unit size: 044–080 — two characters (e.g. P1), 100–160 — three characters (e.g. P01).

Priority044~080100~160Protection control performedRemark
1P1P01Pressure ratio protection control (discharge-side pressure increase)To control the compressor frequency for prevention of operation with high/low pressure ratio.
2P2P02High pressure increase protection controlTo control the compressor frequency for prevention of high pressure increase.
3P3P03Inverter current protection controlTo control the compressor frequency for prevention of inverter current increase in the outdoor unit during operation.
4P4P04Inverter fin temperature increase protection controlTo control the compressor frequency for prevention of inverter fin temperature increase. The inverter fin temperature is detected at the O.U. main PCB.
5P5P05Discharge temperature increase protection controlTo control the compressor frequency for prevention of discharge gas temperature increase during operation.
6P6P06Low pressure decrease protection controlTo control the compressor frequency for prevention of low pressure decrease.
7PdP0dLow pressure increase protection controlTo control the compressor frequency for prevention of low pressure increase.
8PAP0ADemand current controlTo control the compressor frequency for fixing the inverter primary current around the set value (40~100% of rated current).
9P9P09High pressure decrease protection controlTo control the compressor frequency for prevention of high pressure decrease, which would interrupt smooth refrigerant distribution to indoor unit with different height and oil supply to the compressor.