Outdoor unit
Function Change Procedure
Change functions ONLY when the outdoor unit is stopped.
1
Entering settings mode
How to enter depends on unit capacity:
• 4-8 kW: hold PSW3 for approx. 4 seconds.
• 10-16 kW: set DIP switch DSW2-5 to ON.
The function code (e.g. FA) will appear on the 7-segment display.
• 4-8 kW: hold PSW3 for approx. 4 seconds.
• 10-16 kW: set DIP switch DSW2-5 to ON.
The function code (e.g. FA) will appear on the 7-segment display.
2
Selecting a function
Use the PSW2 / PSW3 buttons to scroll between functions (FA, Ni, GH, GC...).
3
Changing the value
Press PSW1 to change the function value (00 / 01).
4
Confirming
Hold PSW3 for approx. 4 seconds.
Buttons: PSW1 = change value (00/01) • PSW2 = next function • PSW3 = previous function
Factory default for all functions: "00" (Inactive / No setting). Note down the number of each function you change.
Function list (7-segment code)
1FACirculation function at Thermo-OFF (heating)
2NiNight Shift (night mode / low noise)
3GHCancel outdoor temp. limit for heating
4GCCancel outdoor temp. limit for cooling
5JoDefrosting for cold zones (changed condition)
6E-SLo defrost setting (IU fan speed)
7HTCancel Hot Start
8cUPerformance priority mode — cooling
9hUPerformance priority mode — heating
10SCEnergy saving mode — cooling
11SHEnergy saving mode — heating
12dBLow noise setting
13dEDemand function setting
14UEWave function setting
15FELow outlet temp. protection — cooling 1
16FcLow outlet temp. protection — cooling 2
17E1Heat exchanger superheat setting
18CoCapacity / test setting
19F1Oil heater function
20F2Capacity / test setting
21F3~F5No function
Details of important functions
Jo — Defrosting for cold zones
00: standard control
01: defrost condition 2 for cold areas
Changes the defrost start/stop temperature thresholds. Set 01 in regions with prolonged frost, where standard defrosting is too infrequent.
01: defrost condition 2 for cold areas
Changes the defrost start/stop temperature thresholds. Set 01 in regions with prolonged frost, where standard defrosting is too infrequent.
cU — Cooling performance priority
00: normal
01: raised max. compressor frequency (cooling only)
Max. frequency [Hz] at cU=1: all models → 90 Hz
(at cU=0: 044/060/080/100/140 = 75 Hz; 120/160 = 85 Hz)
Use when cooling performance seems insufficient.
01: raised max. compressor frequency (cooling only)
Max. frequency [Hz] at cU=1: all models → 90 Hz
(at cU=0: 044/060/080/100/140 = 75 Hz; 120/160 = 85 Hz)
Use when cooling performance seems insufficient.
hU — Heating performance priority
00: normal
01: raised target compressor frequency (heating only)
Increases heating performance, especially at low outdoor temperatures. Values depend on ambient temperature (Ta) and unit capacity (2.0–6.0 HP). E.g. 160 (6.0HP): 95 → 99 Hz at Ta < -15°C.
01: raised target compressor frequency (heating only)
Increases heating performance, especially at low outdoor temperatures. Values depend on ambient temperature (Ta) and unit capacity (2.0–6.0 HP). E.g. 160 (6.0HP): 95 → 99 Hz at Ta < -15°C.
Test Run
11.3.7 — Test Run
Run the test run with the outdoor unit stopped, in normal mode. Not available during other settings.
Start the test: hold PSW1 + PSW3 for 3 seconds.
Cancel the test: hold PSW1 + PSW3 for 3 seconds.
Heating and cooling test available. Control as in normal operation.
Start the test: hold PSW1 + PSW3 for 3 seconds.
Cancel the test: hold PSW1 + PSW3 for 3 seconds.
Heating and cooling test available. Control as in normal operation.
In case of an alarm, the "T." indication is replaced by the alarm code. When finished, do NOT forget to exit Test Run — set T. to 0 or hold PSW1 + PSW3.