R32

Stop codes

Indicator L

0OKOperation stopped = switched off with the button
1OKThermostat off
2ERRORAlarm
3OKAnti-freeze or anti-overheat protection
5ERROROutdoor unit power supply problem – Reset
6ERRORIndoor unit power supply problem – Reset
7OKCooling: stopped due to too low outdoor temp.
Heating: stopped due to too high outdoor temp.
8ERRORCompressor problem
9OK4-way valve switching, unit stop
10OKForced shutdown
11WARNINGResume – pressure problem

Indicator R

12WARNINGResume – low pressure problem
13WARNINGResume – high pressure problem
14WARNINGResume – abnormal compressor voltage
15WARNINGResume – compressor/discharge temp. too high or suction pressure too low
16WARNINGResume – discharge temperature problem
17WARNINGResume – inverter disconnection
18WARNINGResume – due to voltage problems
19OKOperation mode change

Cause Code of Inverter Stoppage (iTC)

044~080

ITCStoppage CauseCorresponding cause code of I.U. or O.U. stoppageIndication during retryAlarm code
1IPM Error17P.753
2Instantaneous Overcurrent17P.748
3Inverter Fin Thermistor Protection Activation17P.754
5Inverter Voltage Decrease18P.806
6Overvoltage18P.806
8Abnormal fault of sampling circuit17P.751
13Open Phase Detection18P.855
18Protection Device activation (PSH)13P.302
21Step-Out Detection17P.753
22EEPROM Error or Abnormal of Key Parameters of Compressor and PFC18P.855
23Abnormal PFC Hardware17P.753
25Abnormal Communication18--
26Power overload18--
28Abnormal Speed of DC Fan18P.857
30Instantaneous Overcurrent of PFC18--
31Instantaneous Overvoltage PFC Generatrix18--
32Abnormal TFIN Sensor17P.754
33Abnormal Chip Check18P.855
36Abnormal AC Voltage18--
Undefined Function18--

Cause of failure — details

Stoppage CauseITCCause of failure
IPM Error1The instantaneous current of the compressor output is too large, triggering the hardware protection.
Instantaneous Overcurrent2The compressor outputs overcurrent, and software protection is triggered when the effective value exceeds 13A.

The compressor outputs instantaneous overcurrent, and software protection is triggered when the peak value exceeds 22A.
Inverter Fin Thermistor Protection Activation3The IPM temperature is too high, check whether the IPM is in good contact with the fin.
Inverter Voltage Decrease5The DC bus voltage is too low, check the input power voltage.
Overvoltage6The DC bus voltage is too high, check the input power voltage.
Abnormal fault of sampling circuit8The O.U. main PCB PFC sampling circuit is damaged, and the O.U. main PCB needs to be replaced.
Open Phase Detection13There is no current or leakage of current in one phase of the three-phase output of the compressor. Please check
1. Whether the wiring of the compressor is correct;
2. Whether one phase of the compressor is open circuit;
3. Whether there is major leakage current between the compressor winding and Ground.
Protection Device activation (PSH)18High pressure switch circuit triggers protection, please check
1. Check whether the wiring of the high pressure switch is correct;
2. The high pressure is too high, causing the pressure switch to be activated;
3. The state of the high pressure switch is abnormal.
Step-Out Detection21The demagnetization of the compressor causes the compressor to step out. Please confirm whether the compressor is normal.

The actual rotating speed of the compressor does not match the target speed of the inverter, please confirm whether the compressor is normal.
EEPROM Error or Abnormal of Key Parameters of Compressor and PFC22The inverter EEPROM software parameters are faulty, please re-write the software or replace the PCB.

The inverter software parameters are faulty, please re-write the software or replace the PCB.
Abnormal PFC Hardware23PFC hardware overcurrent protection.
Abnormal Communication25Abnormal communication between the inverter and the master control.
Power overload26Compressor output power overload protection.
Abnormal Speed of DC Fan28DC fan abnormal speed protection, please check:
1. Whether the wiring of the DC fan is correct;
2. Whether the DC fan is working, and whether there are foreign objects that prevent it from running;
3. If the DC fan does not work, try to replace the motor.
Instantaneous Overcurrent of PFC30When the whole unit inputs overcurrent and the effective value is greater than 17.5A, the software protection will be triggered.

PFC instantaneous overcurrent, software protection is triggered when the peak value is greater than 40A.
Instantaneous Overvoltage PFC Generatrix31PFC DC bus instantaneous overvoltage fault.
Abnormal TFIN Sensor32The TFIN sensor is faulty, please check
1. TFIN sensor wiring status;
2. Whether the TFIN sensor is faulty, whether there is an open circuit or a short circuit.
Abnormal Chip Check33Please confirm that the software is correct.
Abnormal AC Voltage36The AC input voltage is too high, please check whether the input voltage of the whole unit is normal.

The AC input voltage is too low, please check whether the input voltage of the whole unit is normal.

100~160

ITCStoppage CauseCorresponding cause code of I.U. or O.U. stoppageIndication during retryAlarm code
1IPM Error17P1753
2Instantaneous Overcurrent17P1748
3Inverter Fin Thermistor Protection Activation17P1754
4Electronic Thermal Protection17P1748
5Inverter Voltage Decrease18P1806
6Overvoltage18P1806
8Abnormal fault of sampling circuit17P1751
12Ground Fault Detection from Compressor17P1753
17Communication Error18P1855
18Protection Device activation (PSH)13P1302
19Abnormal Protective Device--38
21Step-Out Detection17P1753
Undefined Function18--

Cause of failure — details

Stoppage CauseITCCause of failure
IPM Error1The instantaneous current of the compressor output is too large, triggering the hardware protection.
Instantaneous Overcurrent2Single phase: the compressor outputs overcurrent, and software protection is triggered when the effective value exceeds 18A (100-120) / 30A (140-160).

Three phase: the compressor outputs instantaneous overcurrent, and software protection is triggered when the peak value exceeds 32.5A (100-120) / 36A (140-160).
Inverter Fin Thermistor Protection Activation3The IPM temperature is too high, check whether the IPM is in good contact with the fin.
Electronic Thermal Protection4The current thermistor detects Overcurrent
Inverter Voltage Decrease5The DC bus voltage is too low, check the input power voltage.
Overvoltage6The DC bus voltage is too high, check the input power voltage.
Abnormal fault of sampling circuit8When the frequency of the inverter passes 15–18Hz, the absolute value of the U phase ± and V phase ± detected by the current sensor is below 1.5A; or the position determines when the peak U-plane current at the end is below 5A.
Ground Fault Detection from Compressor12Inverter PCB detects overcurrent when checking ground fault before compressor starts operation.
Protection Device activation (PSH)18High pressure switch circuit triggers protection, please check
1. Check whether the wiring of the high pressure switch is correct;
2. The high pressure is too high, causing the pressure switch to be activated;
3. The state of the high pressure switch is abnormal.
Step-Out Detection21The demagnetization of the compressor causes the compressor to step out. Please confirm whether the compressor is normal.

The actual rotating speed of the compressor does not match the target speed of the inverter, please confirm whether the compressor is normal.