WP1 pump
Shimge
0Damaged pump PWM interfaceShort circuit in the iPWM interfaceERROR
2Standby – pump ready to operate—OK
5–75Pump running normally
Flow information available—OK
Flow information available—OK
80Abnormal operating mode
Pump running but not reaching optimal performance• Voltage drop 160/170–194 V
• Thermal protection trippedERROR
Pump running but not reaching optimal performance• Voltage drop 160/170–194 V
• Thermal protection trippedERROR
85Abnormal operating mode
Pump stopped• Voltage drop < 160/170 V
• Overvoltage > 250 V
• Unexpected external flowERROR
Pump stopped• Voltage drop < 160/170 V
• Overvoltage > 250 V
• Unexpected external flowERROR
90Abnormal operating mode
Pump stopped but functional• Fault in a component other than the pump
• Contamination in the system
• Incorrect temperature setpointERROR
Pump stopped but functional• Fault in a component other than the pump
• Contamination in the system
• Incorrect temperature setpointERROR
95Pump stopped due to permanent failure• Pump blocked
• Electrical module faultERROR
• Electrical module faultERROR
100PWM connection problemBreak in the PWM interface circuitERROR
Grundfos
0Damaged pump PWM interfaceShort circuit in the iPWM interfaceERROR
95Standby – pump ready to operate—OK
5–70Pump running normally
Flow information available—OK
Flow information available—OK
75Abnormal operating mode
Pump running but not reaching optimal performance• Voltage drop 160/170–194 V
• Thermal protection trippedERROR
Pump running but not reaching optimal performance• Voltage drop 160/170–194 V
• Thermal protection trippedERROR
80Abnormal operating mode
Pump stopped• Voltage drop < 160/170 V
• Overvoltage > 250 V
• Unexpected external flowERROR
Pump stopped• Voltage drop < 160/170 V
• Overvoltage > 250 V
• Unexpected external flowERROR
85Abnormal operating mode
Pump stopped• Missing-phase or overload protection tripped
• Short-circuit protection trippedERROR
Pump stopped• Missing-phase or overload protection tripped
• Short-circuit protection trippedERROR
90Abnormal operating mode
Pump stopped• Fault in a component other than the pump
• Contamination in the system
• Incorrect temperature setpointERROR
Pump stopped• Fault in a component other than the pump
• Contamination in the system
• Incorrect temperature setpointERROR
100iPWM connection problemBreak in the PWM interface circuitERROR