R32

WP1 pump

Shimge

0Damaged pump PWM interfaceShort circuit in the iPWM interfaceERROR
2Standby – pump ready to operate—OK
5–75Pump running normally
Flow information available
—OK
80Abnormal operating mode
Pump running but not reaching optimal performance
• Voltage drop 160/170–194 V
• Thermal protection tripped
ERROR
85Abnormal operating mode
Pump stopped
• Voltage drop < 160/170 V
• Overvoltage > 250 V
• Unexpected external flow
ERROR
90Abnormal operating mode
Pump stopped but functional
• Fault in a component other than the pump
• Contamination in the system
• Incorrect temperature setpoint
ERROR
95Pump stopped due to permanent failure• Pump blocked
• Electrical module fault
ERROR
100PWM connection problemBreak in the PWM interface circuitERROR

Grundfos

0Damaged pump PWM interfaceShort circuit in the iPWM interfaceERROR
95Standby – pump ready to operate—OK
5–70Pump running normally
Flow information available
—OK
75Abnormal operating mode
Pump running but not reaching optimal performance
• Voltage drop 160/170–194 V
• Thermal protection tripped
ERROR
80Abnormal operating mode
Pump stopped
• Voltage drop < 160/170 V
• Overvoltage > 250 V
• Unexpected external flow
ERROR
85Abnormal operating mode
Pump stopped
• Missing-phase or overload protection tripped
• Short-circuit protection tripped
ERROR
90Abnormal operating mode
Pump stopped
• Fault in a component other than the pump
• Contamination in the system
• Incorrect temperature setpoint
ERROR
100iPWM connection problemBreak in the PWM interface circuitERROR